Recall Register

Simplex Fire Alarm Control Panels Recalled by Tyco Safety Products Westminster Due to Failure to Alert Monitoring Centers

CPSC recall 11721. Recall date: . Last publish date of the CPSC notice: .

Hazard, in the words of CPSC

The recalled fire alarm control panels can fail to send a signal to alert monitoring centers in the event of a fire.

Remedy, in the words of CPSC

Building managers should contact SimplexGrinnell for a free software upgrade. SimplexGrinnell is contacting its customers directly.

CPSC recall 11721 has the recall date 8 Feb 2011. The notice names the firm Tyco Safety Products Westminster. The recall has about 540 units. The median CPSC recall of 2011 has 12,000 units. This register puts the recall under the hazard Fire. CPSC gives the product type Fire or Smoke Alarms.

Federal law prohibits any person from selling products subject to a Commission ordered recall or a voluntary recall undertaken in consultation with the CPSC.

CPSC publishes these words. Source: CPSC recall notices, section About the U.S. CPSC, read on . The hazard, the remedy and the incident text on this site are the words of the CPSC recall notice. Newest CPSC recall on the register: .

More of the notice

The hazard and the remedy are at the top of the page. Each quotation is the text of CPSC.

CPSC recall 11721: incidents, units, products and firms
Incidents and injuries
The firm has received 2 reports of alarms failing to alert monitoring centers. No injuries have been reported.
Units540
Remedy optionsNew Instructions
Description
The recalled fire alarm panel is the Simplex 4100U-NXP panel configured for third party monitoring and running software revision 14.01. The words "Simplex," "4100U" and "Fire Control" appear on the fire alarm's front panel. The software revision number can be identified by pressing the "Menu" key on the panel keypad, selecting "Show Software Revision Level" and pressing "Enter."
ProductSimplex Fire Alarm Control Panel, About 540, Fire or Smoke Alarms
Sold atDistributed by SimplexGrinnell from May 2010 to September 2010 for between $10,000 and $20,000.
ManufacturerTyco Safety Products Westminster
Made inUnited States

Recall notice: The page that CPSC publishes for one recall of a consumer product. It states the product, the hazard, the remedy and the incidents.

Hazard: The way a product can cause harm, in the words of the CPSC recall notice. This site also puts each recall under short hazard names.

Remedy: What the manufacturer or the firm does about a recalled product. The agency record states the remedy of each recall.

Units: The number of vehicles or products that a recall can include. The manufacturer or the firm reports the number to the agency.

The recall in context

Units in this recall
540Median of 2011: 12,000
CPSC recalls of 2011
313
Recalls of 2011 with one of the same hazards
26%
Recalls of 2011 in the category Fire or Smoke Alarms
0%
Recalls on the register that name Tyco Safety Products Westminster
1

Official channels

Cite this page

Recall Register. CPSC recall 11721. https://recallregister.com/product/832-simplex-fire-alarm-control-panels-recalled-by-tyco-safety-products-wes/. Source: CPSC Recall Retrieval Web Services. Data through .

Sources

Source
US Consumer Product Safety Commission
Licence
US government work, public domain
Data retrieved
1 Oct 2026
Newest CPSC recall on the register
24 Sep 2026

The CPSC notice is the authority. The hazard names come from the hazard text of CPSC. The category is the product type that CPSC gives. How the register is made. Report an error.

Questions

Does CPSC recall 11721 report injuries?
The CPSC notice says: The firm has received 2 reports of alarms failing to alert monitoring centers. No injuries have been reported.
Where was the product sold?
The CPSC notice says: Distributed by SimplexGrinnell from May 2010 to September 2010 for between $10,000 and $20,000.
Which remedy options does CPSC list for recall 11721?
CPSC lists 1 remedy option: New Instructions
How many units are in CPSC recall 11721?
The CPSC notice gives this number: About 540