Recall Register

Carrier® Recalls to Repair Commercial Rooftop HVAC Units Due to Fire Hazard (Recall Alert)

CPSC recall 18731. Recall date: .

Hazard, in the words of CPSC

The HVAC's humidimizer fan can fail to shut off when a connected smoke detector is tripped, posing a fire hazard.

Remedy, in the words of CPSC

Purchasers should immediately contact their Carrier dealer for a free repair, which consists of free replacement and installation of the electronic control board. The firm is contacting all known purchasers.

CPSC recall 18731 has the recall date 19 Mar 2018. The notice names the firm Carrier México, S.A. de C.V. The recall has about 530 units. The median CPSC recall of 2018 has 7,200 units. This register puts the recall under the hazard Fire.

Federal law prohibits any person from selling products subject to a Commission ordered recall or a voluntary recall undertaken in consultation with the CPSC.

CPSC publishes these words. Source: CPSC recall notices, section About the U.S. CPSC, read on . The hazard, the remedy and the incident text on this site are the words of the CPSC recall notice. Newest CPSC recall on the register: .

More of the notice

The hazard and the remedy are at the top of the page. Each quotation is the text of CPSC.

CPSC recall 18731: incidents, units, products and firms
Incidents and injuries
Carrier has received one report of a fan not shutting off during installation testing. No injuries have been reported.
Units530
Remedy optionsRepair
Description
This recall involves Carrier WeatherExpert 6-23 ton, 48/50 series, light commercial rooftop HVAC units intended for use in commercial and institutional buildings and that have a factory installed dehumidification feature. The model numbers are 48/50LC07-26 with an A in the 6th digit and a 0 (zero) in the 14th digit of the model number (e.g., 48LCTA24F2M5-0S1B3). Note that dashes should be counted as digits in the model number. The serial numbers are 1214P to 3317P. The model and serial number can be found on the unit rating plate located on the back of the unit.
ProductCarrier WeatherExpert commercial packaged rooftop HVAC units with humidimizer option, About 530
Sold atCarrier distributors nationwide from March 2014 to September 2017 for between $25,000 and $93,000.
ManufacturerCarrier México, S.A. de C.V
ImporterCarrier Corporation
Made inMexico

Recall notice: The page that CPSC publishes for one recall of a consumer product. It states the product, the hazard, the remedy and the incidents.

Hazard: The way a product can cause harm, in the words of the CPSC recall notice. This site also puts each recall under short hazard names.

Remedy: What the manufacturer or the firm does about a recalled product. The agency record states the remedy of each recall.

Units: The number of vehicles or products that a recall can include. The manufacturer or the firm reports the number to the agency.

The recall in context

Units in this recall
530Median of 2018: 7,200
CPSC recalls of 2018
258
Recalls of 2018 with one of the same hazards
27%
Recalls on the register that name Carrier México, S.A. de C.V
1

Official channels

Cite this page

Recall Register. CPSC recall 18731. https://recallregister.com/product/8287-carrier-recalls-to-repair-commercial-rooftop-hvac-units-due-to-fire-ha/. Source: CPSC Recall Retrieval Web Services. Data through .

Sources

Source
US Consumer Product Safety Commission
Licence
US government work, public domain
Data retrieved
30 Sep 2026
Newest CPSC recall on the register
24 Sep 2026

The CPSC notice is the authority. The hazard names come from the hazard text of CPSC. The category is the product type that CPSC gives. How the register is made. Report an error.

Questions

Does CPSC recall 18731 report injuries?
The CPSC notice says: Carrier has received one report of a fan not shutting off during installation testing. No injuries have been reported.
Where was the product sold?
The CPSC notice says: Carrier distributors nationwide from March 2014 to September 2017 for between $25,000 and $93,000.
Which remedy options does CPSC list for recall 18731?
CPSC lists 1 remedy option: Repair
How many units are in CPSC recall 18731?
The CPSC notice gives this number: About 530