Recall Register

Honeywell International Recalls SWIFT® Wireless Gateway Sold with Fire Alarm Systems Due To Failure to Communicate in Fire

CPSC recall 17151. Recall date: .

Hazard, in the words of CPSC

The smoke detectors connected to the gateway can fail to activate properly when significant environmental contaminants are present, posing a risk that consumers will not be alerted to a fire.

Remedy, in the words of CPSC

Contact Honeywell for an update of the firmware on the SWIFT wireless gateway(s) installed on the system. Commercial building customers should continue using the recalled detectors until the firmware is updated.

CPSC recall 17151 has the recall date 12 May 2017. The notice names the firm Honeywell International. The recall has about 900 units. The median CPSC recall of 2017 has 7,000 units. This register puts the recall under the hazard Fire.

Federal law prohibits any person from selling products subject to a Commission ordered recall or a voluntary recall undertaken in consultation with the CPSC.

CPSC publishes these words. Source: CPSC recall notices, section About the U.S. CPSC, read on . The hazard, the remedy and the incident text on this site are the words of the CPSC recall notice. Newest CPSC recall on the register: .

More of the notice

The hazard and the remedy are at the top of the page. Each quotation is the text of CPSC.

CPSC recall 17151: incidents, units, products and firms
Incidents and injuries
None reported
Units900
Remedy optionsRepair
Description
This recall involves the SWIFT wireless gateway sold with fire alarm systems. The gateways are round, white and measure eight inches in diameter. The gateways are the bridge between the fire alarm control panel and the detectors. These systems are used primarily for indoor or covered areas in commercial buildings, such as in office buildings, hotels, industrial facilities, and apartment complexes. The model number and date codes are printed on the back of the gateway on a white label on the circuit board. The gateways have the following brand names, model numbers and date codes. Brand Model Date Code Range NOTIFIER FWSG 10 13 14 through 12 15 16 Fire-Lite W-GATE Gamewell-FCI VW-GATE Honeywell XLS-WSG Johnson Controls JFWSG
ProductSWIFT wireless gateway sold with fire alarm systems, About 900
Sold atHoneywell distributors nationwide between October 2014 and December 2016 for about $440 for the fire alarm system.
ManufacturerHoneywell International Inc
Made inUnited States

Recall notice: The page that CPSC publishes for one recall of a consumer product. It states the product, the hazard, the remedy and the incidents.

Hazard: The way a product can cause harm, in the words of the CPSC recall notice. This site also puts each recall under short hazard names.

Remedy: What the manufacturer or the firm does about a recalled product. The agency record states the remedy of each recall.

Units: The number of vehicles or products that a recall can include. The manufacturer or the firm reports the number to the agency.

The recall in context

Units in this recall
900Median of 2017: 7,000
CPSC recalls of 2017
280
Recalls of 2017 with one of the same hazards
25%
Recalls on the register that name Honeywell International
5

Other recalls of the firm

Official channels

Cite this page

Recall Register. CPSC recall 17151. https://recallregister.com/product/8052-honeywell-international-recalls-swift-wireless-gateway-sold-with-fire/. Source: CPSC Recall Retrieval Web Services. Data through .

Sources

Source
US Consumer Product Safety Commission
Licence
US government work, public domain
Data retrieved
30 Sep 2026
Newest CPSC recall on the register
24 Sep 2026

The CPSC notice is the authority. The hazard names come from the hazard text of CPSC. The category is the product type that CPSC gives. How the register is made. Report an error.

Questions

Does CPSC recall 17151 report injuries?
The CPSC notice says: None reported
Where was the product sold?
The CPSC notice says: Honeywell distributors nationwide between October 2014 and December 2016 for about $440 for the fire alarm system.
Which remedy options does CPSC list for recall 17151?
CPSC lists 1 remedy option: Repair
How many units are in CPSC recall 17151?
The CPSC notice gives this number: About 900