ANSUL Recalls Fire Extinguisher that Could Fail to Operate
CPSC recall 07507. Recall date: . Last publish date of the CPSC notice: .
Hazard, in the words of CPSC
If the fire extinguisher is dropped horizontally from a height of approximately 2 to 3 feet, the pick-up tube could crack at the threads between the pick-up tube adaptor and the stainless steel tube. If a pick-up tube is cracked, the extinguisher can fail to discharge properly when activated, which can put users at risk during a fire.
Remedy, in the words of CPSC
Pick-up tube replacements will be performed during routine annual maintenance. The pick-up tube assembly is inside the extinguisher and cannot be visually inspected without de-pressurizing and disassembling the extinguisher. This work should only be done by an authorized ANSUL® distributor. Owners concerned about an extinguisher prior to the scheduled maintenance, due to signs of physical damage such as dents or scratches, should contact their authorized ANSUL® distributor to request a free replacement.
CPSC recall 07507 has the recall date 13 Nov 2006. The notice names the firm Ansul. The recall has about 154,000 units. The median CPSC recall of 2006 has 15,200 units. This register puts the recall under the hazard Fire. CPSC gives the product type Fire Extinguishers.
Federal law prohibits any person from selling products subject to a Commission ordered recall or a voluntary recall undertaken in consultation with the CPSC.
CPSC publishes these words. Source: CPSC recall notices, section About the U.S. CPSC, read on . The hazard, the remedy and the incident text on this site are the words of the CPSC recall notice. Newest CPSC recall on the register: .
More of the notice
The hazard and the remedy are at the top of the page. Each quotation is the text of CPSC.
| Incidents and injuries | None reported. |
|---|---|
| Units | 154,000 |
| Description | The recall involves K-GUARD® Wet Chemical, FLAG FIRE® KITCHEN ONE® Wet Chemical, FLAG FIRE® Water and SENTRY® Water Fire Extinguishers manufactured and shipped between May 2003 and September 9, 2005. The recall program involves pick-up tube replacements in the following extinguishers: Brand Model Part Number(s) K-GUARD® Wet Chemical K01-1 430849 (UL) 430850 (ULC) K01-2 432843 (UL) 432848 (ULC) SENTRY® Water W02-1 430847 (English) 430848 (Spanish/English) FLAG FIRE® KITCHEN ONE® Wet Chemical KS-6000 552055 (UL) 552500 (ULC) FLAG FIRE® Water PWS-25G 552050 (UL) 552501 (ULC) Model numbers can be found on the fire extinguisher labels. Affected models meet the following criteria: The year 2004 or 2005 is stamped on the hanger hook attachment on the shell. For 2003 models, information on specific serial numbers included in the recall can be found at www.ansul.com for the K-GUARD Wet Chemical and SENTRY Water extinguishers, or at www.pyrochem.com for the FLAG FIRE and KITCHEN ONE Wet Chemical extinguishers. Contact the firm to determine if your extinguisher is included in this replacement program. |
| Product | K-GUARD®, SENTRY® and FLAG FIRE® Model Fire Extinguishers, About 154,000, Fire Extinguishers |
| Sold at | Ansul Incorporated, through its authorized fire equipment distributors, from May 2003 through September 2005. Extinguishers were sold by distributors to their end users for about $150 to $225 each for the kitchen units and for about $100 each for the water units. |
| Manufacturer | Ansul Incorporated |
| Made in | United States |
Recall notice: The page that CPSC publishes for one recall of a consumer product. It states the product, the hazard, the remedy and the incidents.
Hazard: The way a product can cause harm, in the words of the CPSC recall notice. This site also puts each recall under short hazard names.
Remedy: What the manufacturer or the firm does about a recalled product. The agency record states the remedy of each recall.
Units: The number of vehicles or products that a recall can include. The manufacturer or the firm reports the number to the agency.
The recall in context
- Units in this recall
- 154,000Median of 2006: 15,200
- CPSC recalls of 2006
- 319
- Recalls of 2006 with one of the same hazards
- 29%
- Recalls of 2006 in the category Fire Extinguishers
- 1%
- Recalls on the register that name Ansul
- 1
Official channels
- CPSC recall notice 07507The notice on the CPSC site, with the pictures and the contact of the firm.
- CPSC recallsThe list of all recall notices on the CPSC site.
- SaferProducts.govThe CPSC site for a report about a consumer product.
Follow by RSS:Fire Extinguishers recallsConsumer product recalls
Cite this page
Recall Register. CPSC recall 07507. https://recallregister.com/product/3779-ansul-recalls-fire-extinguisher-that-could-fail-to-operate/. Source: CPSC Recall Retrieval Web Services. Data through .
Sources
- Source
- US Consumer Product Safety Commission
- Licence
- US government work, public domain
- Data retrieved
- 30 Sep 2026
- Newest CPSC recall on the register
- 24 Sep 2026
The CPSC notice is the authority. The hazard names come from the hazard text of CPSC. The category is the product type that CPSC gives. How the register is made. Report an error.
Questions
- Does CPSC recall 07507 report injuries?
- The CPSC notice says:
None reported.
- Where was the product sold?
- The CPSC notice says:
Ansul Incorporated, through its authorized fire equipment distributors, from May 2003 through September 2005. Extinguishers were sold by distributors to their end users for about $150 to $225 each for the kitchen units and for about $100 each for the water units.
- How many units are in CPSC recall 07507?
- The CPSC notice gives this number:
About 154,000
- Where was the product made?
- The CPSC notice gives:
United States