Recall Register

Tyco Fire & Security Recalls Smoke Detectors for Replacement

CPSC recall 06550. Recall date: . Last publish date of the CPSC notice: .

Hazard, in the words of CPSC

The smoke detectors could experience reduced sensitivity to smoke in conditions of high humidity and high temperature. If this occurs, these detectors could delay detecting the presence of smoke in the event of a fire.

Remedy, in the words of CPSC

Commercial building owners and managers with recalled smoke detectors will be contacted by one of the distributors to verify that the detectors in their fire detection system are included in the recall and, if so, to arrange for a free replacement.

CPSC recall 06550 has the recall date 19 May 2006. The notice names the firm Solectron (Suzhou) Technology. The recall has about 128,000 units. The median CPSC recall of 2006 has 15,200 units. This register puts the recall under the hazard Fire. CPSC gives the product type Smoke Detectors/Alarms.

Federal law prohibits any person from selling products subject to a Commission ordered recall or a voluntary recall undertaken in consultation with the CPSC.

CPSC publishes these words. Source: CPSC recall notices, section About the U.S. CPSC, read on . The hazard, the remedy and the incident text on this site are the words of the CPSC recall notice. Newest CPSC recall on the register: .

More of the notice

The hazard and the remedy are at the top of the page. Each quotation is the text of CPSC.

CPSC recall 06550: incidents, units, products and firms
Incidents and injuries
None reported.
Units128,000
Description
These are smoke detectors installed in commercial buildings throughout the U.S. after August 1, 2004. The model numbers listed below are included. Building owners and managers with these smoke detectors will be contacted. 4098-9601 4098-9685 4098-9688C 4098-9601C 4098-9685C 430696 4098-9601EA 4098-9686 T360-9002 4098-9602 4098-9686C 430559 4098-9602C 4098-9687 430695 4098-9605 4098-9688 ADT-3201 T360-9935 430562 ADT-3202 T360-9936 430560 ADT-3204 T360-9001 T360-9003 ADT-3205
ProductTyco Fire & Security Smoke Detectors, About 128,000 smoke detectors, Smoke Detectors/Alarms
ManufacturerSolectron (Suzhou) Technology Co. Ltd
DistributorSimplexGrinnell LP; ADT Security Services Inc; Ansul Inc
Made inChina

Recall notice: The page that CPSC publishes for one recall of a consumer product. It states the product, the hazard, the remedy and the incidents.

Hazard: The way a product can cause harm, in the words of the CPSC recall notice. This site also puts each recall under short hazard names.

Remedy: What the manufacturer or the firm does about a recalled product. The agency record states the remedy of each recall.

Units: The number of vehicles or products that a recall can include. The manufacturer or the firm reports the number to the agency.

The recall in context

Units in this recall
128,000Median of 2006: 15,200
CPSC recalls of 2006
319
Recalls of 2006 with one of the same hazards
29%
Recalls of 2006 in the category Smoke Detectors/Alarms
1%
Recalls on the register that name Solectron (Suzhou) Technology
2

Other recalls of the firm

Other CPSC recalls that name Solectron (Suzhou) Technology
DateRecall
19 May 2006Tyco Fire & Security Recall to Upgrade Software of Fire Detection Systems

Official channels

Cite this page

Recall Register. CPSC recall 06550. https://recallregister.com/product/3419-tyco-fire-security-recalls-smoke-detectors-for-replacement/. Source: CPSC Recall Retrieval Web Services. Data through .

Sources

Source
US Consumer Product Safety Commission
Licence
US government work, public domain
Data retrieved
30 Sep 2026
Newest CPSC recall on the register
24 Sep 2026

The CPSC notice is the authority. The hazard names come from the hazard text of CPSC. The category is the product type that CPSC gives. How the register is made. Report an error.

Questions

Does CPSC recall 06550 report injuries?
The CPSC notice says: None reported.
How many units are in CPSC recall 06550?
The CPSC notice gives this number: About 128,000 smoke detectors
Where was the product made?
The CPSC notice gives: China
How many CPSC recalls name Solectron (Suzhou) Technology?
2 CPSC recalls on this register name Solectron (Suzhou) Technology. This recall is 1 of them.