Recall Register

CPSC, Kidde Announce Recall of Industrial Fire Extinguishers

CPSC recall 05589. Recall date: . Last publish date of the CPSC notice: .

Hazard, in the words of CPSC

The nylon valves on these extinguishers can separate from the steel cylinder during the 6-year recharge service or shortly afterwards, creating a safety hazard to fire extinguisher service personnel and consumers.

Remedy, in the words of CPSC

Fire Extinguisher Distributors and Service Organizations must immediately stop servicing all units covered under this Alert. Kidde has instituted a Fire Extinguisher Replacement Program ("Replacement Program") for all units covered by this Alert. If you are a Fire Extinguisher Distributor or Service Organization and you have not already received a copy of the Replacement Program, as outlined in Service Bulletin 007, please contact Kidde. Only professional Fire Extinguisher Distributors and Service Organizations should remove the affected units and the steps as outlined in the Replacement Program must be followed.

CPSC recall 05589 has the recall date 26 Jul 2005. The notice names the firm Walter Kidde Portable Equipment. The recall has about 470,000 units. The median CPSC recall of 2005 has 14,000 units. This register puts the recall under the hazard Fire. CPSC gives the product type Fire Extinguishers.

Federal law prohibits any person from selling products subject to a Commission ordered recall or a voluntary recall undertaken in consultation with the CPSC.

CPSC publishes these words. Source: CPSC recall notices, section About the U.S. CPSC, read on . The hazard, the remedy and the incident text on this site are the words of the CPSC recall notice. Newest CPSC recall on the register: .

More of the notice

The hazard and the remedy are at the top of the page. Each quotation is the text of CPSC.

CPSC recall 05589: incidents, units, products and firms
Incidents and injuries
Kidde has received five reports of valve separation during either technical service of the units or shortly afterwards, resulting in three reports of injuries.
Units470,000
Description
This Alert involves all Kidde 10 lb. dry chemical fire extinguishers manufactured with a black plastic Zytel® nylon valve assembly and a steel cylinder, between 1991 and 2000. These units were the subject of Kidde Service Bulletin 007 issued on July 21, 2004. These units were designed for commercial and industrial applications, and the majority of these units were placed into service in factories, plants, businesses and other commercial locations, as they require service by a qualified Fire Extinguisher Distributor or Service Organization every 6 years. Some of these units are in use in residential settings. The affected extinguishers have a steel cylinder with a welded neck ring and are between 19 to 21 inches tall, as depicted in the image below. This Alert does not apply to Kidde's smaller 2 1/2 and 5 lb. residential fire extinguishers.
ProductKidde 10 lb. industrial dry chemical fire extinguishers with black plastic Zytel® nylon valves in steel cylinders manufactured between 1991 and 2000, About 470,000, Fire Extinguishers
Sold atCommercial fire equipment distributors and stores nationwide, between 1991 and 2000.
ManufacturerWalter Kidde Portable Equipment Inc
Made inUnited States

Recall notice: The page that CPSC publishes for one recall of a consumer product. It states the product, the hazard, the remedy and the incidents.

Hazard: The way a product can cause harm, in the words of the CPSC recall notice. This site also puts each recall under short hazard names.

Remedy: What the manufacturer or the firm does about a recalled product. The agency record states the remedy of each recall.

Units: The number of vehicles or products that a recall can include. The manufacturer or the firm reports the number to the agency.

The recall in context

Units in this recall
470,000Median of 2005: 14,000
CPSC recalls of 2005
323
Recalls of 2005 with one of the same hazards
23%
Recalls of 2005 in the category Fire Extinguishers
0%
Recalls on the register that name Walter Kidde Portable Equipment
7

Other recalls of the firm

Official channels

Cite this page

Recall Register. CPSC recall 05589. https://recallregister.com/product/3115-cpsc-kidde-announce-recall-of-industrial-fire-extinguishers/. Source: CPSC Recall Retrieval Web Services. Data through .

Sources

Source
US Consumer Product Safety Commission
Licence
US government work, public domain
Data retrieved
30 Sep 2026
Newest CPSC recall on the register
24 Sep 2026

The CPSC notice is the authority. The hazard names come from the hazard text of CPSC. The category is the product type that CPSC gives. How the register is made. Report an error.

Questions

Does CPSC recall 05589 report injuries?
The CPSC notice says: Kidde has received five reports of valve separation during either technical service of the units or shortly afterwards, resulting in three reports of injuries.
Where was the product sold?
The CPSC notice says: Commercial fire equipment distributors and stores nationwide, between 1991 and 2000.
How many units are in CPSC recall 05589?
The CPSC notice gives this number: About 470,000
Where was the product made?
The CPSC notice gives: United States