Recall Register

CPSC, Schneider Electric North American Division Announce Recall of AFCIs

CPSC recall 05035. Recall date: . Last publish date of the CPSC notice: .

Hazard, in the words of CPSC

An AFCI is an electrical circuit protection device (circuit breaker) that detects electrical arcs from cracked, broken or damaged electrical insulation and shuts off power to the circuit before the arcing leads to a fire. An electronic component failure inside the AFCIs can cause the devices to not detect an electrical arc. Although the AFCIs will function as regular circuit breakers, they may not detect an arc fault, posing a safety risk to consumers.

Remedy, in the words of CPSC

Installed AFCIs will be replaced free of charge through electrical contractors. Consumers can return uninstalled AFCIs to the retailers or distributor from whom the unit was purchased for a free replacement unit.

CPSC recall 05035 has the recall date 3 Nov 2004. The notice names the firm Schneider Electric North American Division. The recall has about 700,000 units. The median CPSC recall of 2004 has 13,500 units. This register puts the recall under the hazard Fire. CPSC gives the product type Arc Fault Circuit Interrupters (AFCI).

Federal law prohibits any person from selling products subject to a Commission ordered recall or a voluntary recall undertaken in consultation with the CPSC.

CPSC publishes these words. Source: CPSC recall notices, section About the U.S. CPSC, read on . The hazard, the remedy and the incident text on this site are the words of the CPSC recall notice. Newest CPSC recall on the register: .

More of the notice

The hazard and the remedy are at the top of the page. Each quotation is the text of CPSC.

CPSC recall 05035: incidents, units, products and firms
Incidents and injuries
Schneider Electric is investigating one reported fire during a new home construction that may be related to this problem. No injuries have been reported.
Units700,000
Description
The recalled Square D QO® and Homeline® Arc Fault Interrupter circuit breakers are used with 15- and 20-amp branch circuits. They are required to be installed in bedroom circuits in accordance with the 2002 National Electrical Code. The recalled units were manufactured after March 1, 2004, and have a blue test button. The AFCI circuit breakers have one of the following date codes - CN, DN, EN, FN, GN, HN, or JN - stamped in red on the breaker label located just above the wiring terminal. The recalled units also have one of the following catalog numbers printed on a label on the front of the breaker: QO115AFI, QO115AFIC, QO120AFI, QO120AFIC, QOB115AFI, QOB120AFI, HOM115AFI, HOM115AFIC, HOM120AFI, HOM120AFIC, QO115VHAFI, QO120VHAFI, QOB115VHAFI, or QOB120VHAFI.
ProductArc Fault Circuit Interrupters (AFCI), About 700,000, Arc Fault Circuit Interrupters (AFCI)
Sold atElectrical distributors and retailers sold the AFCIs between March 2004 and September 2004 for between $30 and $130.
ManufacturerSchneider Electric North American Division
Made inMexico

Recall notice: The page that CPSC publishes for one recall of a consumer product. It states the product, the hazard, the remedy and the incidents.

Hazard: The way a product can cause harm, in the words of the CPSC recall notice. This site also puts each recall under short hazard names.

Remedy: What the manufacturer or the firm does about a recalled product. The agency record states the remedy of each recall.

Units: The number of vehicles or products that a recall can include. The manufacturer or the firm reports the number to the agency.

The recall in context

Units in this recall
700,000Median of 2004: 13,500
CPSC recalls of 2004
278
Recalls of 2004 with one of the same hazards
28%
Recalls of 2004 in the category Arc Fault Circuit Interrupters (AFCI)
0%
Recalls on the register that name Schneider Electric North American Division
1

Official channels

Cite this page

Recall Register. CPSC recall 05035. https://recallregister.com/product/2810-cpsc-schneider-electric-north-american-division-announce-recall-of-afc/. Source: CPSC Recall Retrieval Web Services. Data through .

Sources

Source
US Consumer Product Safety Commission
Licence
US government work, public domain
Data retrieved
30 Sep 2026
Newest CPSC recall on the register
24 Sep 2026

The CPSC notice is the authority. The hazard names come from the hazard text of CPSC. The category is the product type that CPSC gives. How the register is made. Report an error.

Questions

Does CPSC recall 05035 report injuries?
The CPSC notice says: Schneider Electric is investigating one reported fire during a new home construction that may be related to this problem. No injuries have been reported.
Where was the product sold?
The CPSC notice says: Electrical distributors and retailers sold the AFCIs between March 2004 and September 2004 for between $30 and $130.
How many units are in CPSC recall 05035?
The CPSC notice gives this number: About 700,000
Where was the product made?
The CPSC notice gives: Mexico