Recall Register

CPSC, Thomas & Betts Announce Recall of Emergency Exit Signs

CPSC recall 03520. Recall date: . Last publish date of the CPSC notice: .

Hazard, in the words of CPSC

The emergency exit signs have an internal electrical component that could overheat and fail, when connected to 277-volt electrical systems, and melt the enclosure, posing a fire hazard.

Remedy, in the words of CPSC

Building managers with recalled emergency exit signs should contact Thomas & Betts to request a free repair kit.

CPSC recall 03520 has the recall date 5 Feb 2003. The notice names the firm Thomas & Betts. The recall has about 31,000 units. The median CPSC recall of 2003 has 9,900 units. This register puts the recall under 2 hazards. The first is Fire. CPSC gives the product type Lights & Signs (Emergency & Exit).

Federal law prohibits any person from selling products subject to a Commission ordered recall or a voluntary recall undertaken in consultation with the CPSC.

CPSC publishes these words. Source: CPSC recall notices, section About the U.S. CPSC, read on . The hazard, the remedy and the incident text on this site are the words of the CPSC recall notice. Newest CPSC recall on the register: .

More of the notice

The hazard and the remedy are at the top of the page. Each quotation is the text of CPSC.

CPSC recall 03520: incidents, units, products and firms
Incidents and injuries
There have been 19 reports of these emergency exit signs overheating and smoking or causing melted or damaged enclosures. No injuries have been reported.
Units31,000
Description
The recalled exit signs were sold under the Lightalarms, Emergi-Lite, and Dynaray brand names and can be installed in either 120-volt or 277-volt applications. Only signs with a red LED and installed in 277-volt applications need to be repaired. These emergency exit signs could be installed in public buildings such as schools, offices and shopping centers to mark an exit in the event of a power failure and loss of lighting. They have a white or black plastic housing and are 13 ½ inches long, 8-3/8 inches high and 2-7/8 inches deep. Recalled units have a raised bead around the edge of the front face and a rectangular rocker switch on the bottom. The product make, model, and date code is located on a label inside the enclosure. The recalled emergency exit signs were manufactured between January 1997 and June 1999.
ProductEmergency Exit Signs, About 31,000, Lights & Signs (Emergency & Exit)
Sold atThe emergency exit signs were sold nationwide by electrical wholesalers and distributors for between $75 and $80.
DistributorThomas & Betts Corporation

Recall notice: The page that CPSC publishes for one recall of a consumer product. It states the product, the hazard, the remedy and the incidents.

Hazard: The way a product can cause harm, in the words of the CPSC recall notice. This site also puts each recall under short hazard names.

Remedy: What the manufacturer or the firm does about a recalled product. The agency record states the remedy of each recall.

Units: The number of vehicles or products that a recall can include. The manufacturer or the firm reports the number to the agency.

The recall in context

Units in this recall
31,000Median of 2003: 9,900
CPSC recalls of 2003
215
Recalls of 2003 with one of the same hazards
31%
Recalls of 2003 in the category Lights & Signs (Emergency & Exit)
0%
Recalls on the register that name Thomas & Betts
1

Official channels

Cite this page

Recall Register. CPSC recall 03520. https://recallregister.com/product/2473-cpsc-thomas-betts-announce-recall-of-emergency-exit-signs/. Source: CPSC Recall Retrieval Web Services. Data through .

Sources

Source
US Consumer Product Safety Commission
Licence
US government work, public domain
Data retrieved
30 Sep 2026
Newest CPSC recall on the register
24 Sep 2026

The CPSC notice is the authority. The hazard names come from the hazard text of CPSC. The category is the product type that CPSC gives. How the register is made. Report an error.

Questions

Does CPSC recall 03520 report injuries?
The CPSC notice says: There have been 19 reports of these emergency exit signs overheating and smoking or causing melted or damaged enclosures. No injuries have been reported.
Where was the product sold?
The CPSC notice says: The emergency exit signs were sold nationwide by electrical wholesalers and distributors for between $75 and $80.
How many units are in CPSC recall 03520?
The CPSC notice gives this number: About 31,000