CPSC, Trane Company Announce Recall of Voyager Heating and Air Conditioning Systems
CPSC recall 01507. Recall date: . Last publish date of the CPSC notice: .
Hazard, in the words of CPSC
One of the three internal flue gas tubes extending from the heat exchanger can separate from the heat exchanger. This could allow flue gases, including carbon monoxide, to enter the building airstream. This could result in serious injury or death to building occupants.
Remedy, in the words of CPSC
Call the local independent Trane or American Standard dealer for a free inspection and replacement, if needed. Trane will completely replace the heat exchanger end plate and internal flue gas tube assemblies in all recalled units at no cost to the consumer.
CPSC recall 01507 has the recall date 24 Jan 2001. The notice names the firm The Trane Company, of Tyler, Texas, a division of American Standard Companies. The recall has about 967 units. The median CPSC recall of 2001 has 22,500 units. This register puts the recall under the hazard Carbon monoxide. CPSC gives the product type Air Conditioners.
Federal law prohibits any person from selling products subject to a Commission ordered recall or a voluntary recall undertaken in consultation with the CPSC.
CPSC publishes these words. Source: CPSC recall notices, section About the U.S. CPSC, read on . The hazard, the remedy and the incident text on this site are the words of the CPSC recall notice. Newest CPSC recall on the register: .
More of the notice
The hazard and the remedy are at the top of the page. Each quotation is the text of CPSC.
| Incidents and injuries | None reported. |
|---|---|
| Units | 967 |
| Description | The Voyager series of light commercial rooftop air conditioners with electric cooling and gas-fired heat exchangers, which are installed in schools and commercial applications, have 120,000 to 135,00 BTU heating capacity and three- to five-ton cooling capacity in horizontal and downflow configurations. The Voyager series has been manufactured by Trane since 1988 and is distributed under the Trane® and American Standard® brand names. The recalled units were manufactured between June 1, 2000 and August 16, 2000 and have serial numbers beginning with R21 through and including R33. The recalled products include the following model designations: YCD036C1H_ _ _ YCD060CWH_ _ _ YCD048C1H_ _ _ YCH060C1H_ _ _ YCH048C1H_ _ _ YCH060C3H_ _ _ YCD060C1H_ _ _ YCH060C4H_ _ _ YCD060C1H_ _ _ YCD060C3H_ _ _ YCD060C4H_ _ _ A name plate bearing each unit's model and serial number is located on the outside sheet metal at the end of the unit where the propeller fan is visible on top, directly to the left of the exposed outdoor coils. |
| Product | Trane Voyager Series Combination Gas Furnace and Electric Air Conditioning Units, 967, Air Conditioners |
| Manufacturer | The Trane Company, of Tyler, Texas, a division of American Standard Companies Inc |
Recall notice: The page that CPSC publishes for one recall of a consumer product. It states the product, the hazard, the remedy and the incidents.
Hazard: The way a product can cause harm, in the words of the CPSC recall notice. This site also puts each recall under short hazard names.
Remedy: What the manufacturer or the firm does about a recalled product. The agency record states the remedy of each recall.
Units: The number of vehicles or products that a recall can include. The manufacturer or the firm reports the number to the agency.
The recall in context
- Units in this recall
- 967Median of 2001: 22,500
- CPSC recalls of 2001
- 245
- Recalls of 2001 with one of the same hazards
- 3%
- Recalls of 2001 in the category Air Conditioners
- 1%
- Recalls on the register that name The Trane Company, of Tyler, Texas, a division of American Standard Companies
- 1
Official channels
- CPSC recall notice 01507The notice on the CPSC site, with the pictures and the contact of the firm.
- CPSC recallsThe list of all recall notices on the CPSC site.
- SaferProducts.govThe CPSC site for a report about a consumer product.
Follow by RSS:Air Conditioners recallsConsumer product recalls
Cite this page
Recall Register. CPSC recall 01507. https://recallregister.com/product/1904-cpsc-trane-company-announce-recall-of-voyager-heating-and-air-conditio/. Source: CPSC Recall Retrieval Web Services. Data through .
Sources
- Source
- US Consumer Product Safety Commission
- Licence
- US government work, public domain
- Data retrieved
- 30 Sep 2026
- Newest CPSC recall on the register
- 24 Sep 2026
The CPSC notice is the authority. The hazard names come from the hazard text of CPSC. The category is the product type that CPSC gives. How the register is made. Report an error.
Questions
- Does CPSC recall 01507 report injuries?
- The CPSC notice says:
None reported.
- How many units are in CPSC recall 01507?
- The CPSC notice gives this number:
967