Recall Register

Siemens Recalls Temperature and Humidity Sensors for Schools, Hospitals and Other Buildings Due to Fire Hazard

CPSC recall 13720. Recall date: . Last publish date of the CPSC notice: .

Hazard, in the words of CPSC

The sensors can overheat, posing a fire hazard.

Remedy, in the words of CPSC

Consumers should look to see if their sensors are currently operating on an AC power source and, if they are, consumers should immediately have the recalled sensors converted to a DC power source. Consumers should contact Siemens to schedule the installation of a free replacement sensor. Siemens is directly contacting owners of the recalled sensors.

CPSC recall 13720 has the recall date 22 Jan 2013. The notice names the firm Siemens Industry. The recall has about 57,000 units. The median CPSC recall of 2013 has 6,500 units. This register puts the recall under 2 hazards. The first is Fire. CPSC gives the product type Thermostats/Thermometers/Sensors.

Federal law prohibits any person from selling products subject to a Commission ordered recall or a voluntary recall undertaken in consultation with the CPSC.

CPSC publishes these words. Source: CPSC recall notices, section About the U.S. CPSC, read on . The hazard, the remedy and the incident text on this site are the words of the CPSC recall notice. Newest CPSC recall on the register: .

More of the notice

The hazard and the remedy are at the top of the page. Each quotation is the text of CPSC.

CPSC recall 13720: incidents, units, products and firms
Incidents and injuries
Four incidents of overheating and fires have been reported to Siemens. Two of the fires were in schools and two in hospitals. Minor damage was reported. No injuries have been reported.
Units57,000
Remedy optionsReplace
Description
This recall involves wall-mounted Q-series sensors that control heat, air conditioning and humidity inside commercial buildings, hospitals and schools. The sensors come in three designs: a blank cover, a cover with a digital display screen or a cover with a digital display screen and door. The sensors are either white or beige and have a Siemens, Talon, Staefa Control System, Staefa Control System/Talon logo or no logo. The recalled model numbers begin with QAA and QFA, and one with SB1. They are: QAA 2060, QAA 2063, QAA 2072, QAA 2073, QFA 2000, QFA 2001, QFA 2060, QFA 2071, QFA2072, QFA 3000, QFA 3001, QFA 3060, QFA 3071, and SB1-0834. The model number is located on the sensor's circuit board inside the unit.
ProductQ-Series Temperature and Humidity Sensors, About 57,000, Thermostats/Thermometers/Sensors
Sold atSiemens sales offices, partners, resellers and installers from June 2007 through August 2012 for between $200 and $400.
ManufacturerSiemens Industry, Inc
Made inChina, United States

Recall notice: The page that CPSC publishes for one recall of a consumer product. It states the product, the hazard, the remedy and the incidents.

Hazard: The way a product can cause harm, in the words of the CPSC recall notice. This site also puts each recall under short hazard names.

Remedy: What the manufacturer or the firm does about a recalled product. The agency record states the remedy of each recall.

Units: The number of vehicles or products that a recall can include. The manufacturer or the firm reports the number to the agency.

The recall in context

Units in this recall
57,000Median of 2013: 6,500
CPSC recalls of 2013
290
Recalls of 2013 with one of the same hazards
28%
Recalls of 2013 in the category Thermostats/Thermometers/Sensors
1%
Recalls on the register that name Siemens Industry
3

Other recalls of the firm

Official channels

Cite this page

Recall Register. CPSC recall 13720. https://recallregister.com/product/1492-siemens-recalls-temperature-and-humidity-sensors-for-schools-hospitals/. Source: CPSC Recall Retrieval Web Services. Data through .

Sources

Source
US Consumer Product Safety Commission
Licence
US government work, public domain
Data retrieved
30 Sep 2026
Newest CPSC recall on the register
24 Sep 2026

The CPSC notice is the authority. The hazard names come from the hazard text of CPSC. The category is the product type that CPSC gives. How the register is made. Report an error.

Questions

Does CPSC recall 13720 report injuries?
The CPSC notice says: Four incidents of overheating and fires have been reported to Siemens. Two of the fires were in schools and two in hospitals. Minor damage was reported. No injuries have been reported.
Where was the product sold?
The CPSC notice says: Siemens sales offices, partners, resellers and installers from June 2007 through August 2012 for between $200 and $400.
Which remedy options does CPSC list for recall 13720?
CPSC lists 1 remedy option: Replace
How many units are in CPSC recall 13720?
The CPSC notice gives this number: About 57,000